Isolation and Conversion of Process Voltage or Current Signals
Power Supply and Signal Isolator for 2-Wire Transmitter
Slimline Housing—Only 6 mm (0.24") Wide
Multiple Signal Ranges (DIP-Switch Selectable)
High Accuracy, <0.05% of Span
Fast Response Time <7 ms

View related products - Process Measurement and Control Instruments

Click to scroll below to order See Specs PDF Manuals Related Items View a printer friendly page

The DRSL-DC2 isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC2 can be used for signal conversion of standard process voltage or current signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.

The DRSL-DC2 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. When the input is configured for 2-wire transmitter mode, the DRSL-DC2 provides the current loop supply voltage. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
INPUT
Current Input
    Measurement Range: 0 to 20.5 mA
    Functional Range: 0 to 23 mA
    Programmable Measurement Ranges: 0 to 20 mA and 4 to 20 mA
    Input Voltage Drop: <1.5V
    2-Wire Transmitter Supply: >17V/20 mA
Voltage Input
    Measurement Range: 0 to 10.25V
    Functional Range: 0 to 11.5V/ 0 to 5.75V
    Programmable Measurement Ranges: 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V
    Input Resistance: ≥500 kΩ

OUTPUT
Current Output
    Signal Range: 0 to 20.5 mA (span)
    Programmable Signal Ranges: 0 to 20 mA and 4 to 20 mA
    Load: 23 mA/600 Ω max
    Load Stability: ≤0.01% of span/100 Ω
    Current Limit: ≤28 mA
Voltage Output
    Signal Range: 0 to 10V
    Programmable Signal Ranges: 0 to 10, 2 to 10, 0 to 5 and 1 to 5V
    Load: >10 kΩ min

GENERAL
Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 1.2 W max
Internal Consumption: 0.4 W typical/0.65 W max
Isolation: Input/output/supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
MTBF: >231 years, according to IEC 61709 (SN29500)
Signal/Noise Ratio: >60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Span: Corresponds to the presently selected DIP switch output range
Accuracy: <±0.05% of span
Temperature Coefficient: <±0.01% of span/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity
    NAMUR NE 21, A Criterion, Burst: <±1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm


To Order (Specify Model Number)    
expand list What Other People Bought: When you see this icon, click on it to expand a list of products that other people have bought when they purchased this model.
 
Most Popular Models Highlighted!
 Part Number   Availability   Price   Description    Qty.
Click to expand/minimize a list of what others bought with the DRSL-DC2  DRSL-DC2 2 weeks   376.00    Isolated DIN rail signal conditioner  
 Accessories
Click to expand/minimize a list of what others bought with the DRSL-PWR-RAIL  DRSL-PWR-RAIL 2 weeks   284.00    Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length  
Click to expand/minimize a list of what others bought with the DRSL-PCU  DRSL-PCU 2 weeks   195.00    Power connector unit, 24 Vdc/2.5 A output to power rail  
    DRSL-MOD-STOP 2 weeks   13.00    Module stop (screwed onto power rail to support and hold mounted devices)  
All dollar amounts on this site are shown in Singapore currency.

 Ordering Example: (1) DRSL-DC2 Isolated DIN rail signal conditioner, $376.00,  plus (1) DRSL-MOD-STOP Module stop (screwed onto power rail to support and hold mounted devices), $13.00,  plus (1) DRSL-PCU Power connector unit, 24 Vdc/2.5 A output to power rail, $195.00,  plus (1) DRSL-PWR-RAIL Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length, $284.00, $376.00 + 13.00 + 195.00 + 284.00 = $868

 Related Links - Manual, Related Products
 Product Manual
   Download Installation Guide for Signal Conditioners
   Download DIN Rail Isolators and Signal Conditioners
 Related Products
DRSL-DC1 DRSL-DC1:
Isolated DIN Rail Repeater
DRSL-DC3 DRSL-DC3:
Isolated DIN Rail Signal Conditioner
DRSL-DC4 DRSL-DC4:
Bipolar Isolated DIN Rail Signal Conditioner for Process Signals
DRSL-SP1 DRSL-SP1:
Isolated DIN Rail Repeater/Splitter for Current Signals
DRSL-SP2 DRSL-SP2:
Isolated DIN Rail Signal Conditioner/Splitter for Process Signals
DRSL-SP3 DRSL-SP3:
Bipolar Isolated DIN Rail Signal Conditioner/Splitter for Process Signals
DRSL-LPI_Series DRSL-LPI_Series:
DIN Rail Input Loop-Powered Isolators
DRSL-LPO_Series DRSL-LPO_Series:
DIN Rail 2-Wire Transmitter Isolators
DRSL-TC_Series DRSL-TC_Series:
Thermocouple Input DIN Rail Signal Conditioners
DRSL-RTD_Series DRSL-RTD_Series:
RTD Input DIN Rail Signal Conditioners
DRSL-RTD-LP DRSL-RTD-LP:
RTD Input Non-Isolated DIN Rail Loop-Powered Signal Conditioner
DRSL-TEMP DRSL-TEMP:
Isolated DIN Rail Loop-Powered Temperature Signal Conditioner
DRSL-U DRSL-U:
Isolated Universal Input DIN Rail Signal Conditioner
   
Keywords:Isolated DIN Rail Signal Conditioner

   Back to topBack to top