Cart  |  Contact  |  Help  |  seainfo@dwyeromega.com  | 
Toll-Free in Malaysia: 1800 88 3496
International+65 6415 5353

Isolated DIN Rail Signal Conditioner

DRSL-DC3

Isolated DIN Rail Signal Conditioner | DRSL-DC3

Isolated DIN Rail Signal Conditioner

SGD335.08 DRSL-DC3

CE
  • Isolation and Conversion of Process Voltage or Current Signals
  • Slimline Housing—Only 6 mm (0.24") Wide
  • Multiple Signal Ranges (DIP-Switch Selectable)
  • High Accuracy, <0.2% of Span
  • Fast Response Time <7 ms
Process Measurement and Control Instruments - View related products

Description

The DRSL-DC3 isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC3 can be used for signal conversion of standard process voltage or current signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.

The DRSL-DC3 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
INPUT
Current Input
    Measurement Range: 0 to 20.5 mA
    Functional Range: 0 to 23 mA
    Programmable Measurement Ranges: 0 to 20 mA and 4 to 20 mA
    Input Voltage Drop: < 1.5V
Voltage Input
    Measurement Range: 0 to 10.25V
    Functional Range: 0 to 11.5V/ 0 to 5.75V
    Programmable Measurement Ranges: 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V
    Input Resistance: ≥500 kΩ

OUTPUT
Current Output
    Signal Range: 0 to 20.5 mA (span)
    Programmable Signal Ranges: 0 to 20 mA and 4 to 20 mA
    Load: 23 mA/600 Ω max
    Load Stability: ≤0.01% of span/ 100 Ω
    Current Limit: ≤28 mA
Voltage Output
    Signal Range: 0 to 10V
    Programmable Signal Ranges: 0 to 10, 2 to 10, 0 to 5 and 1 to 5V
    Load: >10 kΩ min

GENERAL
Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 0.8 W max
Internal Consumption: 0.4 W typical/ 0.65 W max
Isolation: Input/Output/Supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
MTBF: >249 years, according to IEC 61709 (SN29500)
Signal/Noise Ratio: >60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Span: Corresponds to the presently selected DIP switch output range
Accuracy: <±0.2% of span
Temperature Coefficient: <±0.015% of span/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity
    NAMUR NE 21, A Criterion, Burst: <±1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5”)
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
(Specify Model Number)

What Other People Bought: When you see this icon, click on it to expand a list of products that other people have bought when they purchased this model.

Part Number/Desc.
Qty
Description
  
DRSL-DC3
SGD335.08
Availability: 1 week
 
Isolated DIN rail signal conditioner
Accessories
DRSL-PWR-RAIL
DRSL-PWR-RAIL
SGD284.00
Availability: 1 week
 
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
DRSL-PCU
DRSL-PCU
SGD191.64
Availability: 1 week
 
Power connector unit, 24 Vdc/2.5 A output to power rail
  
DRSL-MOD-STOP
SGD13.00
Availability: 1 week
 
Module stop (screwed onto power rail to support and hold mounted devices)
All prices on this site are shown in Singapore Dollars.
Ordering Example: (1) DRSL-DC3 Isolated DIN rail signal conditioner, SGD335.08  plus (1) DRSL-MOD-STOP Module stop (screwed onto power rail to support and hold mounted devices), SGD13.00  plus (1) DRSL-PCU Power connector unit, 24 Vdc/2.5 A output to power rail, SGD191.64  plus (1) DRSL-PWR-RAIL Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length, SGD284.00, SGD335.08 + 13.00 + 191.64 + 284.00 = SGD823.72

Product Manuals:

Download Installation Guide for Signal Conditioners
Download DIN Rail Isolators and Signal Conditioners
We noticed you are from the US. Visit your local site for regional offers and live support.