Application
• The 0 to 5 AAC RMS range makes it possible to accurately measure a typical current transformer.
• The 0 to 300 Vac RMS range allows accurate supply voltage monitoring.
• DRST-AC measures standard input ranges, and can be freely configured to customer-defined input range.
• Converts narrow AC current/voltage inputs to wide bipolar or unipolar outputs, e.g. 0 to 1 VAMS input = ±10 volt or 4 to 20 mA output with a minimum span of 0.5 AAC RMS or 0.5 Vac RMS.
• Configurable input limits control the output value for increased safety. Technical Characteristic
• The latest analog and digital techniques are used to obtain maximum accuracy and immunity to interference.
• Possibility of output safety feedback by selecting S4 to 20 mA output.
• The current output can drive up to 800 Ω, with an adjustable response time of 0.0 to 60.0 seconds.
• Exceptional mA output load stability of <0.001% of span/100 Ω .
• Meets the NAMUR NE21 recommendations, ensuring high accuracy in harsh EMC environments.
• Meets the NAMUR NE43 recommendations, allowing the control system to easily detect an input error.
• Each unit is tested to a high 2.3 kVac, 3-port galvanic isolation level.
• Excellent signal to noise ratio of > 60 dB. Mounting/Installation/Programming
• Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
• Configuration, monitoring, 2-point process calibration and more are accomplished using either the 4501 detachable display or the 4511 detachable digital communication enabler.
• All programming can be password-protected.
Specifications Environmental Conditions Operating Temperature: -20 to 60°C Calibration Temperature: 20 to 28°C Relative Humidity: < 95% RH (non-cond.) Protection Degree: IP20 Installation In: Pollution degree 2 and measurement/overvoltage cat. II Mechanical Specifications Dimensions (HxWxD): 109 x 23.5 x 104 mm Dimensions (HxWxD) w/ 4501/4511: 109 x 23.5 x 116 / 131 mm Weight Approx: 250 g Weight incl. 4501/4511 (approx.): 285 g / 350 g DIN Rail Type: DIN EN 60715/35 mm Wire Size: 0.13 to 2.08 mm 2 AWG 26 to 14 stranded wire Screw Terminal Torque: 0.5 Nm Vibration: IEC 60068-2-6 2 to 13.2 Hz: ±1 mm 13.2 to 100 Hz: ±0.7 g Common Specifications Supply Supply Voltage, Universal: 21.6 to 253 Vac, 50 to 60 Hz or 19.2 to 300 Vdc Max. Required Power: ≤ 1.8 W nom. Internal Power Dissipation: ≤ 2.5 W Isolation Voltage Test Voltage: 2.3 kVac
Working Voltage: 250 Vac (reinforced)/500 Vac (basic) Response Time Response Time (0...90%, 100...10%): < 0.75 s Programming:Communication enabler/Programming front DRSL-DISPLAY Signal Dynamics, Input: 20 bit Signal Dynamics, Output: 18 bit
Signal/Noise Ratio: > 60 dB Output Referred Common Mode Rejection Ratio" 0.02 ppm/VHz Accuracy: Better than 0.3% of selected range* EMC Immunity Influence: < ±0.5% of span*
Extended EMC immunity: NAMUR NE21, A Criterion, Burst: < ±1% of span* Of Span: = of selected standard range Input Specifications Current Input Signal Range: 0 to 5 AAC/40 to 400 Hz Maximum Input Limit: 6.00 AAC @ 40°C Programmable Measurement Ranges: 0 to 0.5; 0 to 1; 0 to 2.5 and 0 to 5 AAC
Custom Configurable Signal Range: 0 to 5 AAC/40 to 400 Hz Min. Measurement Range (Span): 0.5 AAC Input Resistance: Nom. < 0.07 Ω Voltage Input Signal Range: 0 to 300 Vac/40 to 400 Hz Programmable Measurement Ranges:0 to 0.5, 0 to 1, 0 to 2.83, 0 to 5, 0 to 120, 0 to 230 and 0 to 300 Vac
Custom Configurable Signal Range: 0 to 300 Vac/40 to 400 Hz Min. Measurement Range (Span): 0.5 Vac Input Resistance:Nom. 3 MΩ || 100 pF Output Specifications Active Unipolar and Bipolar mA Ooutput Programmable Ranges: 0 to 20, 4 to 20 and S4 to 20 mA Programmable Ranges: ±10 and ±20 mA Programmable Ranges: Direct or Inverted Action Load (@ Current Output): ≤ 800 Ω V-Curve Function, Active Signals, 100-0-100%: 20-0 to 20 mA Passive 2-Wire mA Output Programmable Ranges: 0 to 20 and 4 to 20 mA Programmable Ranges: Direct or Inverted action V-Curve Function, 100-0 to 100%: 20-0 to 20 mA External Loop Supply: 3.5 to 30 V Current Output Signal Range: 0 to 23 mA (unipolar) Signal Range: -23 to +23 mA (bipolar) Current Limit: ≤ 28 mA (unipolar) Current Limit: ± 28 mA (bipolar) Load Stability: ≤ 0.001% of span / 100 Ω Response Time, Programmable: 0.0 to 60.0 s Voltage Output Programmable Signal Ranges: 0/0.2 to 1; 0/1 to 5 ; 0/2 to 10; 1 to 0.2/0; 5 to 1/0; 10 to 2/0 V Programmable Signal Ranges: ±1, ±5 and ±10 V Programmable Signal Ranges: Direct or Inverted Action V-Curve Function, 100-0-100%:1-0-1, 5-0-5 and 10-0-10 V Load (@ Voltage Output): ≥ 500 kΩ
Response Time, Programmable: 0.0 to 60.0 s Observed Authority Requirements EMC: 2014/30/EU LVD: 2014/35/EU RoHS: 2011/65/EU Approvals UL: UL 508 / C22.2 no. 14 NB: For custom configurable signal ranges, general accuracy and EMC specifications are 0.3% of full scale
† All prices on this site are shown in Philippine Pesos.