Cart  |  Contact  |  Help  |  seainfo@dwyeromega.com  | 
Toll-Free in Thailand: 001 800 441 0237
International+65 6415 5353

Isolated DIN Rail Repeater

DRSL-DC1

Isolated DIN Rail Repeater | DRSL-DC1

Isolated DIN Rail Repeater

THB9,005.00 DRSL-DC1

CE
  • Isolation and 1:1 Conversion of Current Signals
  • 1 Current Input—1 Current Output
  • Slimline Housing—Only 6 mm (0.24") Wide
  • Fast Response Time <7 ms
  • High Accuracy, <0.05% of Span
  • Easy-to-Use—No Setup Needed
Process Measurement and Control Instruments - View related products

Description

The DRSL-DC1 isolated repeater provides a competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment. The unit provides isolation and 1:1 conversion of standard current signals.

The unit offers isolation between input, output and supply. Provides surge suppression and protects control systems from transients and noise. The DRSL-DC1 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Measurement ranges are factory calibrated. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
CURRENT INPUT
Measurement Range: 0 to 20.5 mA
Functional Range: 0 to 23 mA
Input Voltage Drop: <1.5 Vdc

CURRENT OUTPUT
Signal Range: 0 to 20.5 mA (span)
Load: 23 mA/600 Ω max
Load Stability: ≤0.01% of span/ 100 Ω (span = 0 to 20 mA)
Current Limit: ≤28 mA

GENERAL
Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 0.8 W max
Internal Consumption: 0.4 W typical/0.65 W max
Isolation: Input/output/supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
MTBF: >284 years, according to IEC 61709 (SN29500)
Signal/Noise Ratio: >60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Accuracy: <±0.05 % of span
Temperature Coefficient: <±0.01% of span/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
(Specify Model Number)

What Other People Bought: When you see this icon, click on it to expand a list of products that other people have bought when they purchased this model.

Part Number/Desc.
Qty
Description
  
DRSL-DC1
THB9,005.00
Availability: 1 week
 
Isolated repeater for current signals
Accessories
DRSL-PWR-RAIL
DRSL-PWR-RAIL
THB7,000.00
Availability: 1 week
 
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
DRSL-PCU
DRSL-PCU
THB4,737.27
Availability: 1 week
 
Power connector unit, 24 Vdc/2.5 A output to power rail
  
DRSL-MOD-STOP
THB319.00
Availability: 1 week
 
Module stop (screwed onto power rail to support and hold mounted devices)
All prices on this site are shown in Thai Baht.
Ordering Example: (1) DRSL-DC1 Isolated repeater for current signals, THB9,005.00  plus (1) DRSL-MOD-STOP Module stop (screwed onto power rail to support and hold mounted devices), THB319.00  plus (1) DRSL-PCU Power connector unit, 24 Vdc/2.5 A output to power rail, THB4,737.27  plus (1) DRSL-PWR-RAIL Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length, THB7,000.00, THB9,005.00 + 319.00 + 4,737.27 + 7,000.00 = THB21,061.27

Product Manuals:

Download Installation Guide for Signal Conditioners
Download DIN Rail Isolators and Signal Conditioners
We noticed you are from the US. Visit your local site for regional offers and live support.